Owens Corning R-Value Guide — Insulation Specifications by Climate Zone

Select the right R-value for your project using current IECC 2021 requirements, real-world performance data, and Owens Corning product recommendations.

Technical Foundation

What R-Value Actually Measures


R-value (thermal resistance) measures a material's resistance to conductive heat flow. Higher R-values indicate greater insulating effectiveness. R-value is measured under steady-state conditions per ASTM C518 at a 75°F mean temperature — the conditions under which Owens Corning products are rated.

Important note on installed performance: Fiberglass batt R-value assumes correct cavity fill, proper batt compression, and no voids or gaps. A correctly installed R-19 batt in a 2×6 cavity will outperform a poorly installed R-21 batt. Continuous insulation layers (FOAMULAR® XPS) are less installation-sensitive because they eliminate cavity gaps.

R-value does not account for air infiltration. In climate zones with significant heating/cooling loads, air sealing should be addressed before or alongside insulation upgrades. The EcoTouch® batt system is compatible with common blower-door-tested air sealing approaches.

Quick Reference: R-Value per Inch

MaterialR-value / inchProduct
Fiberglass BattR-3.1 to R-3.8EcoTouch®
XPS Rigid FoamR-5.0FOAMULAR®
EPS Rigid FoamR-3.6 to R-4.2
Mineral Wool BattR-3.0 to R-3.3
Spray Foam (open)R-3.5 to R-3.7
Spray Foam (closed)R-5.5 to R-6.5

Values per ASTM C518 at 75°F mean. Competitor values are industry typical ranges; verify current third-party data before specification.

IECC 2021 Requirements

Required R-Values by Climate Zone

Based on IECC 2021 residential prescriptive requirements. Commercial and mixed-use requirements vary — contact us for ASHRAE 90.1 guidance.

IECC Zone States (Examples) Attic Min. Wall (2×4) Wall (2×6) Floor OC Recommendation
Zone 1Hawaii, Southern FLR-30R-13R-20R-13EcoTouch® R-30 + R-13 wall
Zone 2FL, TX Gulf, AZR-38R-13R-20R-13EcoTouch® R-38 + R-13
Zone 3TX, GA, NC, NVR-38R-20R-20R-19EcoTouch® R-38 attic + R-20 wall
Zone 4TN, VA, KS, OR, WAR-49R-20R-21R-19EcoTouch® R-49 + R-21 (2×6 preferred)
Zone 5OH, IN, CO, WI, NYR-49R-20+5ciR-21+5ciR-30EcoTouch® R-21 + FOAMULAR® 1" CI
Zone 6MN, ND, MT, NHR-49R-20+5ciR-21+5ciR-30EcoTouch® R-21 + FOAMULAR® 1" CI
Zone 7AK (Fairbanks), CanadaR-49R-20+5ciR-21+5ciR-38EcoTouch® R-21 + FOAMULAR® 2" CI
Zone 8AK (Arctic)R-49R-21+5ciR-21+5ciR-38Custom — contact technical team

Highlighted rows indicate jurisdictions where continuous insulation is prescriptively required. Local jurisdictions may have adopted more stringent amendments; always verify with the AHJ.

Product Selection

Choosing the Right Owens Corning Insulation Product

Attic Insulation (Batt)

EcoTouch® R-38 (10.25") for most Climate Zones 2-4; R-49 (15.25") for Zones 5-7. Verify ventilation requirements — IECC requires a ventilation channel above attic insulation in vented assemblies.

Request Attic Spec Package

Wall Assembly (2×4 or 2×6)

EcoTouch® R-13 fits 2×4 (3.5" cavity); R-19 or R-21 for 2×6 (5.5" cavity). Do not compress batts to fit a shallower cavity — compression reduces effective R-value proportionally.

Request Wall Spec Package

Continuous Insulation (CI)

FOAMULAR® XPS at 1" (R-5) to 4" (R-20) provides a thermal break across the structural layer, eliminating the thermal bridging through studs that reduces a 2×6 wall's nominal R-21 to an effective R-14.

Request CI Spec Package

Need a Project-Specific R-Value Calculation?

Our technical team can provide a full wall and attic assembly calculation showing effective R-value, thermal bridging corrections, and IECC compliance documentation for your specific climate zone.

Request Free Technical Consultation